The SEW 8025 LP is a digital loop and PSC tester used to measure loop impedance and perform wiring checks. It features a 15mA loop measurement that won't trip ELCBs and is easy to use for direct measurements without bypassing wires.   

Request Callback

Order In Bulk

Generate Quote

₹ 14,042.00

(GST inclusive price) i
  • Base Value: ₹ 11900
  • GST: (18) % ₹ 2142
  • Total Value ₹ 14042

₹14,042.00

( - 0% OFF )

Need Help ?

Our Client Care Managers Are On Call 24/7 To Answer Your Question.

Description

Key Features 

  • Battery is not used.
  • 3 ½ digit LCD (2000-count).
  • Backlight function.
  • 15mA loop measurement which will not trip ELCBs.
  • Convenient and easier for users to measure the loop impedance directly without bypassing the wires.
  • Wiring check function.
  • Over temperature protection.
  • Over voltage protection.
  • Built-in voltmeter.
  • Built-in earth tester.
  • Built-in loop/psc tester.
  • Safety standard :
    EN 61010-1 CAT III 300V
    EN 61326-1

 

What's in the Box

  •  SEW 8025 LP

Rating & Reviews

4.5
(Based On 10 Reviews)

Rating

0

0

0

0

0

Product Specifications

SPECIFICATIONS

Loop Impedance
RangeMeasuring rangeNominal test current at 0 Ω external loopAccuracy
20 Ω0.00~19.99 Ω23A / 40ms(2%rdg + 4dgt)
200 Ω0.0~199.9 Ω2.3A / 40ms
2000 Ω0~1999 Ω15mA / 400ms

 

 

 

 

 

 

 

Prospective Short-circuit Current
RangeMeasuring rangeNominal test current at 0 Ω external loopAccuracy
20 KA0.00~4.00 KA23A / 40msConsider accuracy of loop impedance
2000 A0~1999 A23A / 40ms
200 A0.0~199.9 A2.3A / 40ms

 

 

 

 

 

 

 

Voltage Display
Measuring rangeAccuracyRemark
150~260 V(2%rdg + 4dgt)at 0 Ω external loop

 

 

 

 

 

General
Temperature0 ~ 40 °C
System voltage230V (+13%) ( -15%)
System frequency50Hz
None Battery system voltage150V ~ 260V
Over Temperature ProtectionWhen overheating,the " " symbol will show on the LCD, and the 8025LP stop measuring
Wiring checkP-E LEDs illuminate when the wiring polarity of circuit undertest is correct
P-N LEDs illuminate when the wiring polarity of circuit undertest is correct
N-E LED is light when P and N are reversed or the Earth is not connected
15mA Loop measurementLoop impedance 2000Ω range measurement is carried out with low test current (15mA). The current will not cause tripping out for ELCBs.

Rating & Reviews

4.5
(Based On 10 Reviews)

Rating

0

0

0

0

0